SurgeX PF420-POWERFRAME PF420 Powerframe Power Conditioner

OUR PART #: PF420-POWERFRAME

Copied to clipboard

The SurgeX Powerframe 420 provides guaranteed surge protection and power conditioning for audio, video, broadcast and computer equipment. ...Read more

SurgeX PF420-POWERFRAME PF420 Powerframe Power Conditioner Image 1
SurgeX PF420-POWERFRAME PF420 Powerframe Power Conditioner
No longer available at Full Compass
We've left this page up for reference only.

Questions? Contact our
Sales and Service Pros for expert
advice and package pricing.

800-356-5844

Email customer service

Product Overview

The SurgeX Powerframe 420 provides guaranteed surge protection and power conditioning for audio, video, broadcast and computer equipment.

Powerframe 420 units are compact 80 Amp load centers for multi-branch circuit applications. They offer four independent 20 Amp circuits in a 16" x 12" x 4" magnetic shielding NEMA enclosure and meet code for use at the service entrance, sub-panels and in ceiling plenums. The unit features both common mode and normal mode Impedance Tolerant EMI/RFI filtering for a comprehensive power conditioning solution.

SurgeX Advanced Series Mode technology is superior to conventional MOV circuitry or MOV-Hybrid designs and is completely non-sacrificial. Our zero let-through technology provides the most reliable protection available. It stops all surges up to 6,000 volts (unlimited surge current) without producing harmful side effects such as ground contamination or common-mode disturbances.

Features:

  • Magnetic shielding steel enclosure
  • Advanced Series Mode surge protection
  • Advanced Impedance Tolerant EMI/RFI filtering
  • Self-test circuit with visual indicator
  • 10-year warranty
  • Made in U.S.A.

Specifications:

  • Load Rating: 20 amps per circuit @ 120 volts (80 ampstotal)
  • Power Requirement (no load): 15 watts per circuit
  • Surge Let-Through Voltage (6000-volt surge): 0 volts
  • UL 1449 Adjunct Classification Test Results: 1000surges, 6000 volts, 3000 amps, B3 pulse; Measured suppressed voltage: 170volts; no failures.
  • Federal Guidelines: Grade A, Class 1, Mode 1 (CIDA-A-55818)
  • EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB @100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz
  • EMI/RFI Filter, Common Mode (50-ohm load): 18 dB @300 kHz; 30 dB @ 1 MHz; 50 dB @ 5 MHz; 50 dB @ 20 MHz
  • Maximum Applied Surge Voltage: 6000 volts*
  • Maximum Applied Surge Current: Unlimited, due tocurrent limiting
  • Maximum Applied Surge Energy: Unlimited, due tocurrent limiting
  • Endurance (C62.41-1991 Category B3 pulses): 1kV>500,000; 3 kV>10,000; 6 kV>1000
  • Dimensions (H x W x D): 16" x 12" x 4" (40.6 x 30.5 x10.2 cm)
  • Weight: 30 lbs. (13.6 kg)
  • Temperature Range: 5º to 35º C
  • Humidity Range: 5% to 95% R.H., non-condensing
  • Agency Listings: ETL and cETL (UL 1449, 2nd edition; CSA C22.2 No.8-M1986,R2000)